Group 51 FBA SETTINGS
Further fieldbus communication configuration. These parameters need to be set only
if a fieldbus adapter module is installed. See also Appendix A – Fieldbus control on
page 385.
Notes:
This parameter group is presented in the Users Manual of the fieldbus adapter as
parameter group 1 or A.
The new settings will take effect when the drive is powered up the next time
(before powering off the drive, wait at least 1 minute), or when parameter 51.27
FBA PAR REFRESH is activated.
51
51 FBA SETTINGS
51.01 FBA TYPE FW block: None
Displays the type of the connected fieldbus adapter module.
NOT DEFINED Fieldbus adapter module not found (not properly connected, or
disabled by parameter 50.01 FBA ENABLE).
(1) FPBA-xx PROFIBUS-DP adapter module.
(32) FCAN-xx CANopen adapter module.
(37) FDNA-xx DeviceNet adapter module.
51.02 FBA PAR2 FW block: None
……. .
51.26 FBA PAR26 FW block: None
Parameters 51.02…51.26 are adapter module-specific. For more information, see the User’s Manual
of the fieldbus adapter module. Note that not all of these parameters are necessarily visible.
51.27 FBA PAR REFRESH FW block: None
Validates any changed adapter module configuration parameter settings. After refreshing, the value
reverts automatically to (0) DONE.
Note: This parameter cannot be changed while the drive is running.
(0) DONE Refreshing done.
(1) REFRESH Refreshing.
51.28 PAR TABLE VER FW block: None
Displays the parameter table revision of the fieldbus adapter module mapping file stored in the
memory of the drive.
In format xyz, where x = major revision number; y = minor revision number; z = correction number.