Standard function blocks
304
The error codes indicated by the Error output are as follows:
Inputs Message type (Msg Type): INT
Target node or multicast group (Target Node/Grp): INT
Local dataset number (LocalDsNr): INT
Remote dataset number (RemoteDsNr): INT
Outputs Successfully sent messages counter (Sent msg count): DINT
Error output (Error): PB
DS_ReadLocal
(10094)
Illustration
Execution time -
Operation Reads the dataset defined by the LocalDsNr input from the local dataset table. One
dataset contains one 16-bit and one 32-bit word which are directed to the Data1 16B
and Data2 32B outputs respectively.
The LocalDsNr input defines the number of the dataset to be read.
The error codes indicated by the Error output are as follows:
Inputs Local dataset number (LocalDsNr): INT
Bit Description
0 D2D_MODE_ERR: Drive-to-drive communication not activated, or message
type not supported in current drive-to-drive mode (master/follower)
1 LOCAL_DS_ERR: LocalDsNr input out of range (16…199)
2 TARGET_NODE_ERR: Target Node/Grp input out of range (1…62)
3 REMOTE_DS_ERR: Remote dataset number out of range (16…199)
4 MSG_TYPE_ERR: Msg Type input out of range (05)
5…6 Reserved
7 GENERAL_D2D_ERR: Unspecified error in D2D driver
8 RESPONSE_ERR: Syntax error in received response
9 TRA_PENDING: Message has not yet been sent
10 REC_PENDING: Response has not yet been received
11 REC_TIMEOUT: No response received
12 REC_ERROR: Frame error in received message
13 REJECTED: Message has been removed from transmit buffer
14 BUFFER_FULL: Transmit buffer full
DS_ReadLocal
73
TLA1 1 msec (1)
LocalDsNr
Data1 16B
Da ta 1 16B(7 3)
Data2 32B
Da ta 2 32B(7 3)
Error
Error(73)
Bit Description
1 LOCAL_DS_ERR: LocalDsNr out of range (16…199)