EasyManua.ls Logo

ABB ACSM1 - Group 53 FBA DATA out

ABB ACSM1
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters and firmware blocks
186
Group 53 FBA DATA OUT
These parameters select the data to be sent by the fieldbus controller to the drive,
and need to be set only if a fieldbus adapter module is installed. See also Appendix
A – Fieldbus control on page 385.
Notes:
This parameter group is presented in the Users Manual of the fieldbus adapter as
parameter group 2 or B.
The new settings will take effect when the drive is powered up the next time
(before powering off the drive, wait at least 1 minute), or when parameter 51.27
FBA PAR REFRESH is activated.
The maximum number of data words is protocol-dependent.
53
53 FBA DATA OUT
53.01 FBA DATA OUT1 FW block: None
Selects data to be transferred from the fieldbus controller to the drive.
0 Not in use.
1 Control Word (16 bits).
2 Reference REF1 (16 bits).
3 Reference REF2 (16 bits).
11 Control Word (32 bits).
12 Reference REF1 (32 bits).
13 Reference REF2 (32 bits).
1001…9999 Parameter index.
53.02 FBA DATA OUT2 FW block: None
53.12 FBA DATA OUT12 FW block: None
See 53.01 FBA DATA OUT1.

Table of Contents

Other manuals for ABB ACSM1

Related product manuals