Parameters and firmware blocks
77
Group 01 ACTUAL VALUES
This group contains basic actual signals for monitoring the drive.
01
01 ACTUAL VALUES
Firmware block:
ACTUAL VALUES
(1)
1.01 SPEED ACT FW block: SPEED FEEDBACK (page 131)
Filtered actual speed in rpm. Used speed feedback is defined by parameter 22.01 SPEED FB SEL.
Filter time constant can be adjusted by parameter 22.02 SPEED ACT FTIME.
1.02 SPEED ACT PERC FW block: ACTUAL VALUES (see above)
Actual speed in percent of the motor synchronous speed.
1.03 FREQUENCY FW block: ACTUAL VALUES (see above)
Estimated drive output frequency in Hz.
1.04 CURRENT FW block: ACTUAL VALUES (see above)
Measured motor current in A.
1.05 CURRENT PERC FW block: ACTUAL VALUES (see above)
Motor current in percent of the nominal motor current.
1.06 TORQUE FW block: ACTUAL VALUES (see above)
Motor torque in percent of the motor nominal torque.
1.07 DC-VOLTAGE FW block: ACTUAL VALUES (see above)
Measured intermediate circuit voltage in V.
1.08 ENCODER 1 SPEED FW block: ENCODER (page 225)
Encoder 1 speed in rpm.
1.09 ENCODER 1 POS FW block: ENCODER (page 225)
Actual position of encoder 1 within one revolution.
ACTUAL VALUES
14
TLF10 2 msec (1)
1.02 SPEED ACT PERC
1.03 FREQUENCY
1.04 CURRENT
1.05 CURRENT PERC
1.06 TORQUE
1.07 DC-VOLTAGE
1.14 SPEED ESTIMATED
1.15 TEMP INVERTER
1.16 TEMP BC
1.20 BRA KE RES LOAD
1.22 INVERTER POWER
1.26 ON TIME COUNTER
1.27 RUN TIME COUNTER