Parameters and firmware blocks
105
10.02 EXT1 START IN1 FW block: DRIVE LOGIC (see above)
Selects the source 1 for the start and stop commands in external control location EXT1. See
parameter 10.01 EXT1 START FUNC selections (1) IN1 and (2) 3-WIRE.
Note: This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.03 EXT1 START IN2 FW block: DRIVE LOGIC (see above)
Selects the source 2 for the start and stop commands in external control location EXT1. See
parameter 10.01 EXT1 START FUNC selection (2) 3-WIRE.
Note: This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.04 EXT2 START FUNC FW block: DRIVE LOGIC (see above)
Selects the source for the start and stop control in external control location EXT2.
Note: This parameter cannot be changed while the drive is running.
(0) NOT SEL No source selected.
(1) IN1 Source of the start and stop commands are selected by parameter
10.05 EXT2 START IN1. The start/stop is controlled as follows:
(2) 3-WIRE Source of the start and stop commands are selected by parameters
10.05 EXT2 START IN1 and 10.06 EXT2 START IN2. The start/stop is
controlled as follows:
(3) FBA Start and stop control from the source selected by parameter 10.13 FB
CW USED.
(4) D2D Start and stop control from another drive via D2D Control Word.
(5) IN1F IN2R The source selected by 10.05 EXT2 START IN1 is the forward start
signal, the source selected by 10.06 EXT2 START IN2 is the reverse
start signal.
Par. 10.05 Command
0 -> 1 Start
1 -> 0 Stop
Par. 10.05 Par. 10.06 Command
0 -> 1 1 Start
Any 1 -> 0 Stop
Any 0 Stop
Par. 10.05 Par. 10.06 Command
00 Stop
1 0 Start forward
0 1 Start reverse
11 Stop