Parameters and firmware blocks
129
20.08 THERM CURR LIM FW block: None
Enables the thermal current limitation. Thermal current limit is calculated by the inverter thermal
protection function.
(0) ENABLE The calculated thermal current value limits the inverter output current
(i.e. motor current).
(1) DISABLE The calculated thermal limit is not used. If the inverter output current is
excessive, alarm IGBT OVERTEMP is generated and eventually the
drive trips on fault IGBT OVERTEMP.