Parameters and firmware blocks
155
Value pointer: Group and index
32.04 MAXIMUM TORQ REF FW block: TORQ REF MOD (see above)
Defines the maximum torque reference.
0…1000% Maximum torque reference.
32.05 MINIMUM TORQ REF FW block: TORQ REF MOD (see above)
Defines the minimum torque reference.
-1000…0% Minimum torque reference.
32.06 LOAD SHARE FW block: TORQ REF MOD (see above)
Scales the external torque reference to a required level (external torque reference is multiplied by the
selected value).
Note: If local torque reference is used, no load share scaling is applied.
-8…8 External torque reference multiplier.
32.07 TORQ RAMP UP FW block: TORQ REF MOD (see above)
Defines the torque reference ramp-up time, i.e. the time for the reference to increase from zero to the
nominal motor torque.
0…60 s Torque reference ramp-up time.
32.08 TORQ RAMP DOWN FW block: TORQ REF MOD (see above)
Defines the torque reference ramp-down time, i.e. the time for the reference to decrease from the
nominal motor torque to zero.
0…60 s Torque reference ramp-down time.