Parameters and firmware blocks
240
97.07 LQ USER FW block: None
Defines the quadrature axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet motors.
0…10 p.u. (per unit) Quadrature axis (synchronous) inductance.
97.08 PM FLUX USER FW block: None
Defines the permanent magnet flux.
Note: This parameter is valid only for permanent magnet motors.
0…2 p.u. (per unit) Permanent magnet flux.
97.09 RS USER SI FW block: None
Defines the stator resistance R
S
of the motor model.
0.00000…100.00000 ohm Stator resistance.
97.10 RR USER SI FW block: None
Defines the rotor resistance R
R
of the motor model.
Note: This parameter is valid only for asynchronous motors.
0.00000…100.00000 ohm Rotor resistance.
97.11 LM USER SI FW block: None
Defines the main inductance L
M
of the motor model.
Note: This parameter is valid only for asynchronous motors.
0.00…100000.00 mH Main inductance.
97.12 SIGL USER SI FW block: None
Defines the leakage inductance
σL
S
.
Note: This parameter is valid only for asynchronous motors.
0.00…100000.00 mH Leakage inductance.
97.13 LD USER SI FW block: None
Defines the direct axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet motors.
0.00…100000.00 mH Direct axis (synchronous) inductance.
97.14 LQ USER SI FW block: None
Defines the quadrature axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet motors.
0.00…100000.00 mH Quadrature axis (synchronous) inductance.