Fault tracing
286
0307 DEFAULT FILE
(0x6100)
Drive internal fault
Note: This fault cannot be
reset.
Contact your local ABB representative.
0308 APPL FILE PAR CONF
(0x6300)
Corrupted application file
Note: This fault cannot be
reset.
Reload application.
If fault is still active, contact your local ABB
representative.
0309 APPL LOADING
(0x6300)
Corrupted application file
Note: This fault cannot be
reset.
Reload application.
If fault is still active, contact your local ABB
representative.
0310 USERSET LOAD
(0xFF69)
Loading of user set is not
successfully completed
because:
- requested user set does not
exist
- user set is not compatible with
drive program
- drive has been switched off
during loading.
Reload.
0311 USERSET SAVE
(0xFF69)
User set is not saved because
of memory corruption.
Check the setting of parameter 95.01 CTRL
UNIT SUPPLY.
If the fault still occurs, contact your local ABB
representative.
0312 UFF OVERSIZE
(0x6300)
UFF file is too big. Contact your local ABB representative.
0313 UFF EOF
(0x6300)
UFF file structure failure Delete faulty file or contact your local ABB
representative.
0314 TECH LIB INTERFACE
(0x6100)
Incompatible firmware interface
Note: This fault cannot be
reset.
Contact your local ABB representative.
0315 RESTORE FILE
(0x630D)
Restoration of backed-up
parameters failed.
Contact your local ABB representative.
0316 DAPS MISMATCH
(0x5484)
Mismatch between JCU Control
Unit firmware and power unit
logic versions.
Contact your local ABB representative.
0317 SOLUTION FAULT
(0x6200)
Fault generated by function
block SOLUTION_FAULT in the
application program.
Check the usage of the SOLUTION_FAULT
block in the application program.
Code Fault
(fieldbus code)
Cause What to do