EasyManua.ls Logo

ABB ACSM1 - Page 362

ABB ACSM1
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Standard function blocks
362
Operation The output (Q) is set to 1 when the input (IN) has been 1 for a time defined by the pulse
time input (PT). The output is set to 0, when the input is set to 0.
Elapsed time count (TE) starts when the input is set to 1 and stops when the input is set
to 0.
Example:
Inputs Input (IN): Boolean
Pulse time input (PT): DINT (1 = 1 µs)
Outputs Output (Q): Boolean
Elapsed time output (ET): DINT (1 = 1 µs)
TP
(10060)
Illustration
Execution time 1.46 µs
Operation The output (Q) is set to 1 when the input (IN) is set to 1. The output is set to 0, when it
has been 1 for a time defined by the pulse time input (PT).
Elapsed time count (TE) starts when the input is set to 1 and stops when the input is set
to 0.
Inputs Input (IN): Boolean
Pulse time input (PT): DINT (1 = 1 µs)
Outputs Output (Q): Boolean
Elapsed time output (ET): DINT (1 = 1 µs)
IN
Q
PT
PT
ET
ET
ET
TP
88
TLA1 1 msec (1)
PT
>IN
Q
Q(88)
ET
ET(88)
IN
Q
ET
PT
PTPT

Table of Contents

Other manuals for ABB ACSM1

Related product manuals