Chapter 3 Commissioning
3-42 3BSE029382R0101 Rev C
The scaling of analog outputs does not affect the measurement values transferred through
Profibus.
If zero set has been performed, the zero set values are transferred through Profibus.
Scaling of Profibus measurement values, see Section 3.13.5.2.
Each measurement value has 16 bit, 2-complement representation (Integer 16).
3.13.5.1 Miscellaneous Menu
Use this menu to scale Profibus measurement values.
Figure 3-25. Profibus Scaling, One Roll or Two Rolls
To
Miscellaneous
Menu
Profibus On/Off
[ZZ]
ProfibusAddress
[ZZZ]
Profibus On/Off
ZZ
ProfibusAddress
ZZZ
(Only shown if
Profibus is On)
MeasuringRange
Roll 1
(Only shown if
Profibus is On)
ServiceMenu
SetFactory
Default
AreYouSure ActionDone
(shown for 1 s.)
LoadDivision
XXX.XXX N
MeasuringRange
XXX.XXX N
MeasuringRange
[XXX.XXX] N
MeasuringRange
Roll 2
(Only shown if
Profibus is On)
LoadDivision
XXX.XXX N
MeasuringRange
XXX.XXX N
MeasuringRange
[XXX.XXX] N
From DI
1. Profibus Scaling: Two rolls selected in SystemDefinition
This menu is not
shown if One roll
is selected in
SystemDefinition
FastSetUp
WebTension
Presentation-
Menu
SetNominal-
Load
ServiceMenu
ZeroSet
SetWrapGain
> 5 s
AO 1 - AO 6
Miscellaneous
Menu
System-
Definition
ObjectType
DO 1 - DO 4
AI 1 - AI 2
DI