Chapter 6 Fault-tracing
6-6 3BSE029382R0101 Rev C
6.8 Warnings and Errors Detected by the Tension Electronics
6.8.1 Errors
6.8.1.1 Flash Memory Error
Replace PFEA113.
6.8.1.2 EEPROM Memory Error
Replace PFEA113.
6.8.1.3 Supply Error
IP 20-version (unsealed):
When the PFEA113 is connected to the 24 VDC power supply the voltage between terminals
X1:1 and X1:2 should be 18 - 36 V.
If the voltage is lower than 18 V:
Check the power supplies rating. Rating should be 18-36 V DC.
Check that the power supply has sufficient capacity. See power requirements in
Section 2.13.2 Relay Board PXKB 201.
If the power supply has sufficient capacity, check cabling and cable resistance between
power supply and PFEA113.
If power supply and cabling are correct, the tension electronics is probably defect.
Replace PFEA113.
IP 65-version (NEMA 4):
Check the mains voltage connected to terminals X9:1 and X9:2.
Mains voltage must be:
85 - 264 V AC (100 V -15% to 240 V +10%)
Frequency range: 45 - 65 Hz