Section 3.13.5 Handling of Measurement Data through Profibus
3BSE029382R0101 Rev C 3-43
Figure 3-26. Profibus Scaling, Segmented Roll
3.13.5.2 Scaling of Profibus Measuring Values
The Profibus values can be scaled in two ways:
• Default Scaling – scaling that only depends on load cell nominal load.
• User defined Scaling – the scaling of the Profibus values can be set by the user.
Table 3-5. Profibus parameters
Parameter Description
Profibus On/Off The Profibus can be enabled and disabled.
Profibus Address If the Profibus is enabled, the Profibus address
must be set in the range 000 - 125.
Measuring Range If the Profibus is enabled, the Profibus
Measuring Range and load division can be set
for Roll1 and Roll2 separately.
SetFactory
Default
AreYouSure ActionDone
(shown for 1 s.)
MeasuringRange
SegmentedRoll
(Only shown if
Profibus is On)
LoadDivision
XXX.XXX N
MeasuringRange
XXX.XXX N
MeasuringRange
[XXX.XXX] N
Miscellaneous
Menu
Profibus On/Off
[ZZ]
Profibus On/Off
ZZ
2. Profibus Scaling: Segmented roll selected in SystemDefinition
ProfibusAddress
[ZZZ]
ProfibusAddress
ZZZ
(Only shown if
Profibus is On)
To
ServiceMenu
From DI