Tension Electronics PFEA113, User Manual
Chapter 3 Commissioning
3-46 3BSE029382R0101 Rev C
NOTE
After the user has changed the Measuring Range value, the only way to
return to Default scaling, is to use the function Set Factory default in the
Miscellaneous Menu.
3.13.5.3 Filtering of Profibus Measuring Values
Measuring values 1-6 have the same filtering as AO1-AO6.
3.13.5.4 Input Buffer, Communication Block from PFEA113 to PLC
This section specifies measurement values and Boolean values in the input buffer
communication block.
Data
Value 1: AO1 (16 bit 2-complement)
Value 2: AO2 (16 bit 2-complement)
Value 3: AO3 (16 bit 2-complement)
Value 4: AO4 (16 bit 2-complement)
Value 5: AO5 (16 bit 2-complement)
Value 6: AO6 (16 bit 2-complement)
Boolean in (not used bits are set to zero)
Byte No. 13:
The error or warning is active when the corresponding bit is set to “1”.
Data Byte No.
Bit No.
76543210
Value 1
01 MSB
02 LSB
Value 2
03 MSB
04 LSB
Value 3
05 MSB
06 LSB
Value 4
07 MSB
08 LSB
Value 5
09 MSB
10 LSB
Value 6
11 MSB
12 LSB
Boolean in 13 No. 7 No. 6 No. 5 No. 4 No. 3 No. 2 No. 1 No. 0
Boolean in 14 No. 7 No. 6 No. 5 No. 4 No. 3 No. 2 No. 1 No. 0