2.3.1 Common data 1
Table 4: Common data 1
BitA RegA IEC 61850 name SA name Description Values
CTRL.LLN0
2720 170.00 .Loc.stVal - Remote/Local state 0/1=Rem/Loc
2721 170.01 .LocRem.stVal.Station - Station state 1=Station
DR.RDRE1
2722 170.02 .RcdMade.stVal - DR recording made 1=Made
2723 170.03 .mcd
LD0.LLN0
2726 170.06 .SetSeld.stVal Settings reserved 1=Reserved
2727 170.07 .mcd
2728 170.08 .SetChg.stVal Settings changed 1=Changed
2729 170.09 .mcd
2.3.2 LD0.FPHLPTOC1 Three-phase non-directional overcurrent
protection, low stage (1)
Table 5: LD0.FPHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.FPHLPTOC1
3936 246.00 .Str.general START General start 1=Start
3937 246.01 .mcd
3938 246.02 .Str.phsA phsA start 1=Start
3939 246.03 .mcd
3940 246.04 .Str.phsB phsB start 1=Start
3941 246.05 .mcd
3942 246.06 .Str.phsC phsC start 1=Start
3943 246.07 .mcd
3944 246.08 .Op.general OPERATE General operate 1=Operate
3945 246.09 .mcd
Section 2 1MRS757822 B
Modbus data mappings
18 Recloser Protection and Control RER615
Point List Manual