ALARM is red and green for OK. Colors can, however, be reconfigured with a
setting parameter.
GUID-775477F8-C2DE-4138-B2C0-6B7C2774D4D2 V1 EN
Figure 2: Signal wired to either OK or Alarm input
Table 81: LD0.LEDGGIO1 Indication LED states OFF/ColorX
BitA
RegA IEC 61850 name SA name Description Values
LD0.LEDGGIO1
2768 173.00 .ISCSO1.stVal - LED 1 state 0/1=Off/Color
2769 173.01 .ISCSO2.stVal - LED 2 state 0/1=Off/Color
2770 173.02 .ISCSO3.stVal - LED 3 state 0/1=Off/Color
2771 173.03 .ISCSO4.stVal - LED 4 state 0/1=Off/Color
2772 173.04 .ISCSO5.stVal - LED 5 state 0/1=Off/Color
2773 173.05 .ISCSO6.stVal - LED 6 state 0/1=Off/Color
2774 173.06 .ISCSO7.stVal - LED 7 state 0/1=Off/Color
2775 173.07 .ISCSO8.stVal - LED 8 state 0/1=Off/Color
2776 173.08 .ISCSO9.stVal - LED 9 state 0/1=Off/Color
2777 173.09 .ISCSO10.stVal - LED 10 state 0/1=Off/Color
2778 173.10 .ISCSO11.stVal - LED 11 state 0/1=Off/Color
2779 173.11 <reserved> 0
2.3.79 LD0.LEDGGIO1 Indication LED states Color1/Color2
These LED indication points interpret the case when a signal is wired to both the
OK and ALARM inputs, but inverted to the other. This means that the LED toggles
between red and green colors. The default color for ALARM is red and green for
OK. Colors can, however, be reconfigured with a setting parameter.
Section 2 1MRS757822 B
Modbus data mappings
48 Recloser Protection and Control RER615
Point List Manual