2.3.64 LD0.MDSOPT1 Generic operation time supervision (1)
Since the register size is 16 bits, the value saturates at 65535 hours (approximately
7.5 years). Alternatively, a 32-bit user-definable register can be made of this data to
cover the whole 300 000 hours (34 years) range. The value can also, for example,
be rescaled to show “total operation days” instead by changing the scale factor
from 1 to 1/24 = 0.0417.
Table 67: LD0.MDSOPT1 Generic operation time supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.MDSOPT1
3308 205.12 OpTmWrn.stVal WARNING Op. time warning 1=Warning
3309 205.13 .mcd
3310 205.14 OpTmAlm.stVal ALARM Op. time alarm 1=Alarm
3311 205.15 .mcd
2.3.65 LD0.PHSVPR1 Voltage presence supervision (1)
Table 68: LD0.PHSVPR1 Voltage presence supervision (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHSVPR1
3960 247.08 .VLiv.stVal U_LIVE High voltage presence 1=High voltage
3961 247.09 .mcd
3962 247.10 .VLivPhsA.stVal U_A_AB_LIVE High phsA or phsAB voltage 1=High voltage
3963 247.11 .mcd
3964 247.12 .VLivPhsB.stVal U_B_BC_LIVE High phsB or phsBC voltage 1=High voltage
3965 247.13 .mcd
3966 247.14 .VLivPhsC.stVal U_C_CA_LIVE High phsC or phsCA voltage 1=High voltage
3967 247.15 .mcd
3968 248.00 .VDea.stVal U_DEAD Low voltage presence 1=Low voltage
3969 248.01 .mcd
3970 248.02 .VDeaPhsA.stVal U_A_AB_DEAD Low phsA or phsAB voltage 1=Low voltage
3971 248.03 .mcd
3972 248.04 .VDeaPhsB.stVal U_B_BC_DEAD Low phsB or phsBC voltage 1=Low voltage
3973 248.05 .mcd
3974 248.06 .VDeaPhsC.stVal U_C_CA_DEAD Low phsC or phsCA voltage 1=Low voltage
3975 248.07 .mcd
Section 2 1MRS757822 B
Modbus data mappings
40 Recloser Protection and Control RER615