BitA RegA IEC 61850 name SA name Description Values
3135 195.15 .mcd
3136 196.00 .Op.general OPERATE General operate 1=Operate
3137 196.01 .mcd
2.3.35 LD0.FRPFRQ1 Frequency protection (1)
Table 38: LD0.FRPFRQ1 Frequency protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.FRPTRC1
4000 250.00 .Str.general START Stage 1 start 1=Start
4001 250.01 .mcd
LD0.FRPTOF1 Overfrequency
4002 250.02 .Op.general OPR_OFRQ Operate 1=Operate
4003 250.03 .mcd
LD0.FRPTUF1 Underfrequency
4004 250.04 .Op.general OPR_UFRQ Operate 1=Operate
4005 250.05 .mcd
LD0.FRPFRC1 Frequency gradient
4006 250.06 .Op.general OPR_FRG Operate 1=Operate
4007 250.07 .mcd
2.3.36 LD0.FRPFRQ2 Frequency protection (2)
Table 39: LD0.FRPFRQ2 Frequency protection (2)
BitA
RegA IEC 61850 name SA name Description Values
LD0.FRPTRC2
4008 250.08 .Str.general START Stage 2 start 1=Start
4009 250.09 .mcd
LD0.FRPTOF2 Overfrequency
4010 250.10 .Op.general OPR_OFRQ Operate 1=Operate
4011 250.11 .mcd
LD0.FRPTUF2 Underfrequency
4012 250.12 .Op.general OPR_UFRQ Operate 1=Operate
4013 250.13 .mcd
LD0.FRPFRC2 Frequency gradient
4014 250.14 .Op.general OPR_FRG Operate 1=Operate
4015 250.15 .mcd
Section 2 1MRS757822 B
Modbus data mappings
30 Recloser Protection and Control RER615
Point List Manual