2.3.46 LD0.MAPGAPC5 Multipurpose analog protection function
(5)
Table 49: LD0.MAPGAPC5 Multipurpose analog protection function (5)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC5
3712 232.00 .Str.general START Stage start 1 = Start
3713 232.01 .mcd
3714 232.02 .Op.general OPERATE Stage operate 1 = Operate
3715 232.03 .mcd
2.3.47 LD0.MAPGAPC6 Multipurpose analog protection function
(6)
Table 50: LD0.MAPGAPC6 Multipurpose analog protection function (6)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC6
3716 232.04 .Str.general START Stage start 1 = Start
3717 232.05 .mcd
3718 232.06 .Op.general OPERATE Stage operate 1 = Operate
3719 232.07 .mcd
2.3.48 LD0.CMHAI1 Current total demand distortion (1)
Table 51: LD0.CMHAI1 Current total demand distortion (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.CMHAI1
3316 207.04 .Alm.stVal ALARM 1=Alarm
3317 207.05 .mcd
2.3.49 LD0.VMHAI1 Voltage total demand distortion (1)
Table 52: LD0.VMHAI1 Voltage total demand distortion (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.VMHAI1
3318 207.06 .Alm.stVal ALARM 1=Alarm
3319 207.07 .mcd
Section 2 1MRS757822 B
Modbus data mappings
34 Recloser Protection and Control RER615
Point List Manual

Table of Contents