2.3.80 CTRL.CBCSWI1 Circuit breaker (1) mom. position
Table 83: CTRL.CBCSWI1 Circuit breaker (1) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBCSWI1 POSITION
2804 175.04 .Pos.stVal.Close - Close bit 1=Close
2805 175.05 .Pos.stVal.Open - Open bit 1=Open
2806 175.06 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.81 CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
Table 84: CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBCSWI1 POSITION
2816 176.00 .Pos.stVal.Close Close bit 1=Close
2817 176.01 .mcd
2818 176.02 .Pos.stVal.Open Open bit 1=Open
2819 176.03 .mcd
2820 176.04 < reserved >
2821 176.05 < reserved >
2822 176.06 .Pos.stSeld SELECTED CB selected for control 1=Selected
2823 176.07 .mcd
2.3.82 CTRL.CBCILO1 Circuit breaker (1) enable signals
Table 85: CTRL.CBCILO1 Circuit breaker (1) enable signals
BitA
RegA IEC 61850 name SA name Description Values
CTRL.CBCILO1
2824 176.08 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
2825 176.09 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
2.3.83 LD0.XGGIO130 Physical I/O states (BIO card X130)
Table 86: LD0.XGGIO130 Physical I/O states (BIO card X130)
BitA
RegA IEC 61850 name SA name Description Values
LD0.XGGIO130
3184 199.00 .Ind1.stVal X130-Input 1 State 0/1=Off/On
3185 199.01 .mcd
3186 199.02 .Ind2.stVal X130-Input 2 State 0/1=Off/On
Table continues on next page
Section 2 1MRS757822 B
Modbus data mappings
50 Recloser Protection and Control RER615
Point List Manual