2.5.8 LD0.SPCRGGIO1 Multipurpose binary outputs (1)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
Table 151: LD0.SPCRGGIO1 Multipurpose binary outputs (1)
0xA CS IEC 61850 name SA name Description Values
LD0.SPCRGGIO1
2416 - .SPCS01.ctlVal Output 1 control 0/1=Off/On
2417 - .SPCS02.ctlVal Output 2 control 0/1=Off/On
2418 - .SPCS03.ctlVal Output 3 control 0/1=Off/On
2419 - .SPCS04.ctlVal Output 4 control 0/1=Off/On
2420 - .SPCS05.ctlVal Output 5 control 0/1=Off/On
2421 - .SPCS06.ctlVal Output 6 control 0/1=Off/On
2422 - .SPCS07.ctlVal Output 7 control 0/1=Off/On
2423 - .SPCS08.ctlVal Output 8 control 0/1=Off/On
2424 - .SPCS09.ctlVal Output 9 control 0/1=Off/On
2425 - .SPCS10.ctlVal Output 10 control 0/1=Off/On
2426 - .SPCS11.ctlVal Output 11 control 0/1=Off/On
2427 - .SPCS12.ctlVal Output 12 control 0/1=Off/On
2428 - .SPCS13.ctlVal Output 13 control 0/1=Off/On
2429 - .SPCS14.ctlVal Output 14 control 0/1=Off/On
2430 - .SPCS15.ctlVal Output 15 control 0/1=Off/On
2431 - .SPCS16.ctlVal Output 16 control 0/1=Off/On
Section 2 1MRS757822 B
Modbus data mappings
82 Recloser Protection and Control RER615
Point List Manual