BitA RegA IEC 61850 name SA name Description Values
3111 194.07 .mcd
3112 194.08 .Str.phsB phsB start 1=Start
3113 194.09 .mcd
3114 194.10 .Str.phsC phsC start 1=Start
3115 194.11 .mcd
3116 194.12 .Op.general OPERATE General operate 1=Operate
3117 194.13 .mcd
2.3.33 LD0.PSPTUV1 Positive-sequence undervoltage protection
(1)
Table 36: LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PSPTUV1
3118 194.14 .Str.general START General start 1=Start
3119 194.15 .mcd
3120 195.00 .Str.phsA phsA start 1=Start
3121 195.01 .mcd
3122 195.02 .Str.phsB phsB start 1=Start
3123 195.03 .mcd
3124 195.04 .Str.phsC phsC start 1=Start
3125 195.05 .mcd
3126 195.06 .Op.general OPERATE General operate 1=Operate
3127 195.07 .mcd
2.3.34 LD0.NSPTOV1 Negative-sequence overvoltage protection
(1)
Table 37: LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.NSPTOV1
3128 195.08 .Str.general START General start 1=Start
3129 195.09 .mcd
3130 195.10 .Str.phsA phsA start 1=Start
3131 195.11 .mcd
3132 195.12 .Str.phsB phsB start 1=Start
3133 195.13 .mcd
3134 195.14 .Str.phsC phsC start 1=Start
Table continues on next page
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 29
Point List Manual