BitA RegA IEC 61850 name SA name Description Values
3142 196.06 .Str.phsB phsB start 1=Start
3143 196.07 .mcd
3144 196.08 .Str.phsC phsC start 1=Start
3145 196.09 .mcd
3146 196.10 .Op.general OPERATE General operate 1=Operate
3147 196.11 .mcd
2.3.28 LD0.PHPTUV2 Phase undervoltage protection (2)
Table 31: LD0.PHPTUV2 Phase undervoltage protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHPTUV2
3148 196.12 .Str.general START General start 1=Start
3149 196.13 .mcd
3150 196.14 .Str.phsA phsA start 1=Start
3151 196.15 .mcd
3152 197.00 .Str.phsB phsB start 1=Start
3153 197.01 .mcd
3154 197.02 .Str.phsC phsC start 1=Start
3155 197.03 .mcd
3156 197.04 .Op.general OPERATE General operate 1=Operate
3157 197.05 .mcd
2.3.29 LD0.PHPTUV3 Phase undervoltage protection (3)
Table 32: LD0.PHPTUV3 Phase undervoltage protection (3)
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHPTUV3
3158 197.06 .Str.general START General start 1=Start
3159 197.07 .mcd
3160 197.08 .Str.phsA phsA start 1=Start
3161 197.09 .mcd
3162 197.10 .Str.phsB phsB start 1=Start
3163 197.11 .mcd
3164 197.12 .Str.phsC phsC start 1=Start
3165 197.13 .mcd
3166 197.14 .Op.general OPERATE General operate 1=Operate
3167 197.15 .mcd
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 27
Point List Manual