RegA Type Scale IEC 61850 name SA name Description Values
Record 10 data to read: If selected
9351 u16 1 - Record sequence num 1...9999
9352 u16 1 - Unread records left 0...499
Timestamp of record
9353 u16 1 - Year, Month Year/Month
9354 u16 1 - Day, Hour Day/Hour
9355 u16 1 - Minute, Second Min/Sec
9356 u16 1 - Millisecond Millisecond
9357 u16 1 Event identification
1)
9358 u16 1 Data object ID1
1)
9359 u16 1 Data object ID2
1)
9360 u16 1 Event data value 1
1)
9361 u16 1 Event data value 2
1)
1) See the technical manual.
2.4.50 Fault record structure header
Table 141: Fault record structure header
RegA
Type Scale IEC 61850 name SA name Description Values
Selection write:
9401 u16 - Read selection -99...3
Record data header:
9402 u16 - Record sequence num 0...65535
9403 u16 - Unread records left 0...99
Timestamp of record:
9404 u16 - Year, month Year/Month
9405 u16 - Day, hour Day/Hour
9406 u16 - Minute, second Min/Sec
9407 u16 - Millisecond Millisecond
9408 u16
- Timestamp quality
1)
LD0.FLTMSTA1
9409 u16 100 .StrDur.mag - Start duration 0...100.00 [%]
9410 u16 1 .ActSG.stVal - Active setting group 1...6
9411 u16 100 .FltDiskm.mag - Fault distance 0...9999.99
[pu]
9412 u16 < reserved > 0
9413 u16 < reserved > 0
9414 u16 < reserved > 0
9415 u16 < reserved > 0
Table continues on next page
Section 2 1MRS757822 B
Modbus data mappings
76 Recloser Protection and Control RER615
Point List Manual