2.4.47 Time and reason for latest IED reset
Table 138: Time and reason for latest IED reset
RegA Type Scale IEC 61850 name SA name Description Values
9221 u16 1 Year 2000...2999
9222 u16 1 Month 1...12
9223 u16 1 Day 1...31
9224 u16 1 Hour 0...23
9225 u16 1 Minute 0...59
9226 u16 1 Second 0...59
9227 u16 1 Millisecond 0…999
9228 u16 1 Reset reason
9228.0 Bit - bit 0 1=Cold start
9228.1 Bit - bit 1 1=Watchdog
9228.2 Bit - bit 2 1=Warm start
2.4.48 Active parameter setting group - read and write
Table 139: Active parameter setting group - read and write
RegA
Type Scale IEC 61850 name SA name Description Values
9231 u16 1 Active setting group 1...6
2.4.49 Event record structure
Table 140: Event record structure
RegA
Type Scale IEC 61850 name SA name Description Values
Selection write:
9250 u16 1 - Num of multiple records 1...10
9251 i16 1 - Read selection -499…3
Record 1 data to read:
9252 u16 1 - Record sequence num 1...9999
9253 u16 1 - Unread records left 0...499
Timestamp of record
9254 u16 1 - Year, Month Year/Month
9255 u16 1 - Day, Hour Day/Hour
9256 u16 1 - Minute, Second Min/Sec
9257 u16 1 - Millisecond Millisecond
9258 u16 1 Event identification
1)
9259 u16 1 Data object ID1
1)
Table continues on next page
Section 2 1MRS757822 B
Modbus data mappings
72 Recloser Protection and Control RER615
Point List Manual