2.3.7 LD0.DPHHPDOC1 Three-phase directional overcurrent
protection, high stage (1)
Table 10: LD0.DPHHPDOC1 Three-phase directional overcurrent protection, high stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DPHHPTOC1
3026 189.02 .Str.general START General start 1=Start
3027 189.03 .mcd
3028 189.04 .Str.phsA phsA start 1=Start
3029 189.05 .mcd
3030 189.06 .Str.phsB phsB start 1=Start
3031 189.07 .mcd
3032 189.08 .Str.phsC phsC start 1=Start
3033 189.09 .mcd
3034 189.10 .Op.general OPERATE General operate 1=Operate
3035 189.11 .mcd
2.3.8 LD0.FEFLPTOC1 Non-directional earth-fault protection,
low stage (1)
Table 11: LD0.FEFLPTOC1 Non-directional earth-fault protection, low stage (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.FEFLPTOC1
3966 247.14 .Str.general START Stage start 1=Start
3967 247.15 .mcd
3968 248.00 .Opr.general OPERATE Stage operate 1=Operate
3969 248.01 .mcd
2.3.9 LD0.EFHPTOC1 Non-directional earth-fault protection,
high stage (1)
Table 12: LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.EFHPTOC1
2940 183.12 .Str.general START Stage start 1=Start
2941 183.13 .mcd
2942 183.14 .Op.general OPERATE Stage operate 1=Operate
2943 183.15 .mcd
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 21
Point List Manual