2.3.66 LD0.CMMXU1 Phase current limit supervision (1)
Table 69: LD0.CMMXU1 Phase current limit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.CMMXU1
2752 172.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2753 172.01 .mcd
2754 172.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2755 172.03 .mcd
2756 172.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
2757 172.05 .mcd
2758 172.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2759 172.07 .mcd
2.3.67 LD0.RESCMMXU1 Residual current limit supervision (1)
Table 70: LD0.RESCMMXU1 Residual current limit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.RESCMMXU1
2760 172.08 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2761 172.09 .mcd
2762 172.10 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2763 172.11 .mcd
2.3.68 LD0.VMMXU1 Phase voltage limit supervision (1)
Table 71: LD0.VMMXU1 Phase voltage limit supervision (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.VMMXU1
2784 174.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2785 174.01 .mcd
2786 174.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2787 174.03 .mcd
2788 174.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
2789 174.05 .mcd
2790 174.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2791 174.07 .mcd
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 41
Point List Manual