2.4.26 LD0.FMMXU1 Frequency measurement (1)
Table 117: LD0.FMMXU1 Frequency measurement (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.FMMXU1
168 u16 100 .Hz.mag F_DB Frequency
35.00...75.00
[Hz]
2.4.27 Indication bits mirrored in registers
Table 118: Indication bits mirrored in registers
RegA Type Scale IEC 61850 name SA name Description Values
170.00 Bit Indication bit 2720 (0x1700)
170.01 Bit Indication bit 2721 (0x1701)
: : :
170.14 Bit Indication bit 2734 (0x170E)
170.15 Bit Indication bit 2735 (0x170F)
171.00 Bit Indication bit 2736 (0x1710)
2.4.28 LD0.VMSTA1 Voltage demand values (1)
Table 119: LD0.VMSTA1 Voltage demand values (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.VMSTA1 Demand phase-to-ground
1954 u16 1000 .AvVPhsA.mag U_DMD_A - phsA amplitude 0...4.0 [xUn]
1955 u16 1000 .AvVPhsB.mag U_DMD_B - phsB amplitude 0...4.0 [xUn]
1956 u16 1000 .AvVPhsC.mag U_DMD_C - phsC amplitude 0...4.0 [xUn]
Demand phase-to-phase
1957 u16 1000 .AvVPhsAB.mag U_DMD_AB - phsAB amplitude 0...4.0 [xUn]
1958 u16 1000 .AvVPhsBC.mag U_DMD_BC - phsBC amplitude 0...4.0 [xUn]
1959 u16 1000 .AvVPhsCA.mag U_DMD_CA - phsCA amplitude 0...4.0 [xUn]
Update time stamp
1)
1960 u16 - - Year - month
1961 u16 - - Day - hour
1962 u16 - - Minute - second
1963 u16 - - Milliseconds
1964 u16 - - Time quality
1) See the technical manual.
Section 2 1MRS757822 B
Modbus data mappings
64 Recloser Protection and Control RER615
Point List Manual