2.3.37 LD0.T1PTTR1 Thermal overload protection (1)
Table 40: LD0.T1PTTR1 Thermal overload protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.T1PTTR1
2972 185.12 .Str.general START General start 1=Start
2973 185.13 .mcd
2974 185.14 .AlmThm.general ALARM Thermal alarm 1=Alarm
2975 185.15 .mcd
2976 186.00 .Op.general OPERATE General operate 1=Operate
2977 186.01 .mcd
2.3.38 CTRL.CCBRBRF1 Circuit breaker (1) failure protection
Table 41: CTRL.CCBRBRF1 Circuit breaker (1) failure protection
BitA RegA IEC 61850 name SA name Description Values
CTRL.CCBRBRF1
2826 176.10 .InStr.stVal START CBFP start command 1=Start
2827 170.11 .mcd
2828 176.12 .Str.general CB_FAULT_AL Timer running 1=Running
2829 176.13 .mcd
2830 176.14 .OpEx.general TRBU Fail, external trip 1=Ext.trip
2831 176.15 .mcd
2832 177.00 .OpIn.general TRRET Internal re-trip 1=Re-trip
2833 177.01 .mcd
2.3.39 LD0.INRPHAR1 Three-phase inrush detection (1)
Table 42: LD0.INRPHAR1 Three-phase inrush detection (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.INRPHAR1
2964 185.04 .Str.general BLK2H General start 1=Start
2965 185.05 .mcd
2966 185.06 .Str.phsA phsA start 1=Start
2967 185.07 .mcd
2968 185.08 .Str.phsB phsB start 1=Start
2969 185.09 .mcd
2970 185.10 .Str.phsC phsC start 1=Start
2971 185.11 .mcd
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 31
Point List Manual