BitA RegA IEC 61850 name SA name Description Values
4064 254.00 .SPCS09.stVal Ouput state 9 0/1=Off/On
4065 254.01 .mcd
4066 254.02 .SPCS10.stVal Ouput state 10 0/1=Off/On
4067 254.03 .mcd
4068 254.04 .SPCS11.stVal Ouput state 11 0/1=Off/On
4069 254.05 .mcd
4070 254.06 .SPCS12.stVal Ouput state 12 0/1=Off/On
4071 254.07 .mcd
4072 254.08 .SPCS13.stVal Ouput state 13 0/1=Off/On
4073 254.09 .mcd
4074 254.10 .SPCS14.stVal Ouput state 14 0/1=Off/On
4075 254.11 .mcd
4076 254.12 .SPCS15.stVal Ouput state 15 0/1=Off/On
4077 254.13 .mcd
4078 254.14 .SPCS16.stVal Ouput state 16 0/1=Off/On
4079 254.15 .mcd
2.3.76 LD0.GSEGGIO1 Goose supervision (1)
Table 79: LD0.GSEGGIO1 Goose supervision (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.GSEGGIO1
2734 170.14 .Alm.stVal ALARM General alarm 0/1=Off/On
2.3.77 LD0.LEDPTRC1 Global conditioning (1)
Table 80: LD0.LEDPTRC1 Global conditioning (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.LEDPTRC1
2736 171.00 .Str.general - Global start 1=Start
2737 171.01 .mcd
2738 171.02 .Op.general - Global operate 1=Operate
2739 171.03 .mcd
2.3.78 LD0.LEDGGIO1 Indication LED states OFF/ColorX
These LED indication points interpret the case when an indication signal is wired
to either the OK or ALARM input of the LED function block. The default color for
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 47
Point List Manual