EasyManua.ls Logo

ABB Relion RER615 - LD0.VMMXU2 Phase Voltage Limit Supervision (2); LD0.MVGAPC1 Multipurpose Binary Inputs (1)

ABB Relion RER615
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.69 LD0.VMMXU2 Phase voltage limit supervision (2)
Table 72: LD0.VMMXU2 Phase voltage limit supervision (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.VMMXU2
3360 210.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
3361 210.01 .mcd
3362 210.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
3363 210.03 .mcd
3364 210.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
3365 210.05 .mcd
3366 210.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
3367 210.07 .mcd
2.3.70 LD0.MVGAPC1 Multipurpose binary inputs (1)
Table 73: LD0.MVGAPC1 Multipurpose binary inputs (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.MVGAPC1
3536 221.00 .Q1.stVal Input 1 0/1=Off/On
3537 221.01 .mcd
3538 221.02 .Q2.stVal Input 2 0/1=Off/On
3539 221.03 .mcd
3540 221.04 .Q3.stVal Input 3 0/1=Off/On
3541 221.05 .mcd
3542 221.06 .Q4.stVal Input 4 0/1=Off/On
3543 221.07 .mcd
3544 221.08 .Q5.stVal Input 5 0/1=Off/On
3545 221.09 .mcd
3546 221.10 .Q6.stVal Input 6 0/1=Off/On
3547 221.11 .mcd
3548 221.12 .Q7.stVal Input 7 0/1=Off/On
3549 221.13 .mcd
3550 221.14 .Q8.stVal Input 8 0/1=Off/On
3551 221.15 .mcd
Section 2 1MRS757822 B
Modbus data mappings
42 Recloser Protection and Control RER615
Point List Manual

Table of Contents

Other manuals for ABB Relion RER615