BitA RegA IEC 61850 name SA name Description Values
3068 191.12 .PrgCutOut.stVal CUTOUT_INPRO Cutout time in progress 1=In progress
3069 191.13 .mcd
3070 191.14 .FrqOpAlm.stVal FRQ_OP_ALM Frequent op. Alarm 1=Alarm
3071 191.15 .mcd
3072 192.00 .RclTmStr.stVal Reclaim time started
3073 192.01 .mcd
3074 192.02 .ProCrd.stVal Protection coordination 1=In progress
3075 192.03 .mcd
3076 192.04 .CBManCls.stVal MAN_CB_CL CB manually closed 1=CB closed
3077 192.05 .mcd
3078 192.06 .Op.general CLOSE_CB Operate (close XCBR) 1=Close CB
3079 192.07 .mcd
3080 192.08 .OpOpn.general OPEN_CB Operate (open XCBR) 1=Open CB
3081 192.09 .mcd
3082 192.10 .UnsCBCls.stVal UNSUC_CB CB closing failed 1=Failed
3083 192.11 .mcd
3084 192.12 .WtMstr.stVal CMD_WAIT Master signal to follower 1=Signal
3085 192.13 .mcd
2.3.59 LD0.SECRSYN1 Synchrocheck (1)
Table 62: LD0.SECRSYN1 Synchrocheck (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.SECRSYN1
3882 242.10 .SynPrg SYNC_INPRO Synch. in progress 1=In progress
3883 242.11 .mcd
3884 242.12 .FailCmd CMD_FAIL_AL Close request fail 1=Failed
3885 242.13 .mcd
3886 242.14 .FailSyn CL_FAIL_AL Close cmd fail 1=Failed
3887 242.15 .mcd
2.3.60 LD0.SSCBR1 Circuit breaker (1) condition monitoring
Table 63: LD0.SSCBR1 Circuit breaker (1) condition monitoring
BitA
RegA IEC 61850 name SA name Description Values
LD0.SSCBR1
2848 178.00 .OpnAlm.stVal TRV_T_OP_ALM Opn travel time alarm 1=Alarm
2849 178.01 .ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm
2850 178.02 .SprChaAlm.stVal SPR_CHR_ALM Spring charge alarm 1=Alarm
Table continues on next page
Section 2 1MRS757822 B
Modbus data mappings
38 Recloser Protection and Control RER615
Point List Manual