2.4.8 SSR6 System status register (6) control command status
(client-dependent)
Table 99: SSR6 System status register (6) control command status (client-dependent)
RegA Type Scale IEC 61850 name SA name Description Values
Last cmd result code
1)
133.00 Bit - bit 0
133.01 Bit - bit 1
133.02 Bit - bit 2
133.03 Bit - bit 3
133.04 Bit - bit 4
133.05 Bit - bit 5
133.06 Bit - bit 6
133.07 Bit - bit 7
Response Type
1)
133.08 Bit - bit 0
133.09 Bit - bit 1
Command state
1)
133.10 Bit - bit 0
133.11 Bit - bit 1
Cmd sequence number 0...15
133.12 Bit - bit 0
133.13 Bit - bit 1
133.14 Bit - bit 2
133.15 Bit - bit 3
1) See the technical manual.
2.4.9 LD0.T1PTTR1 Thermal protection values (1)
Table 100: LD0.T1PTTR1 Thermal protection values (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.T1PTTR1
146 i16 1 .Tmp.mag TEMP Object temperature
-100.0…
9999.9 [C]
147 u16 1 .TmpRl.mag TEMP_RL Relative temperature
0.00…99.99
[C]
148 i16 1 .TmpUsed.mag TEMP_AMB Ambient temperature
-99…999.99
[C]
149 u16 .001 .TmmsOp.stVal THERMLEV_ST Est. time to operate
0…600,000
[ms]
150 u16 .001 .TmmsRecEna.stVal THERMLEV_END Est. time to deactivate block
0…600,000
[ms]