2.3.53 CTRL.DCSXSWI1 Disconnector position indication (1)
Table 56: CTRL.DCSXSWI1 Disconnector position indication (1)
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI1 POSITION
2792 174.08 .Pos.stVal.Close - Close bit 1=Close
2793 174.09 .Pos.stVal.Open - Open bit 1=Open
2794 174.10 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.54 CTRL.DCSXSWI2 Disconnector position indication (2)
Table 57: CTRL.DCSXSWI2 Disconnector position indication (2)
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI2 POSITION
2795 174.11 .Pos.stVal.Close - Close bit 1=Close
2796 174.12 .Pos.stVal.Open - Open bit 1=Open
2797 174.13 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.55 CTRL.ESSXSWI1 Earthing switch indication (1)
Table 58: CTRL.ESSXSWI1 Earthing switch indication (1)
BitA
RegA IEC 61850 name SA name Description Values
CTRL.ESSXSWI1 POSITION
2801 175.01 .Pos.stVal.Close - Close bit 1=Close
2802 175.02 .Pos.stVal.Open - Open bit 1=Open
2803 175.03 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.56 CTRL.ESSXSWI2 Earthing switch indication (2)
Table 59: CTRL.ESSXSWI2 Earthing switch indication (2)
BitA
RegA IEC 61850 name SA name Description Values
CTRL.ESSXSWI2 POSITION
2807 175.07 .Pos.stVal.Close - Close bit 1=Close
2808 175.08 .Pos.stVal.Open - Open bit 1=Open
2809 175.09 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)