RegA Type Scale IEC 61850 name SA name Description Values
9448 u16 1000 .VoltsCAb.mag - PhsCAb voltage 0...4.00 [xUn]
9449 u16 1000 .VZroSeqb.mag - Zero seq. voltage b 0...4.00 [xUn]
9450 u16 1000 .VPsSeqb.mag - Positive seq. voltage b 0...4.00 [xUn]
9451 u16 1000 .VNgSeqb.mag - Negative seq. voltage b 0...4.00 [xUn]
9452 i16 10 .DifAAngBC.mag - PhsB-C angle -/+ 180 deg
9453 i17 10 .DifBAngCA.mag - PhsC-A angle -/+ 180 deg
9454 i18 10 .DifCAngAB.mag - PhsA-B angle -/+ 180 deg
9455 u16 100 .MaxTmpRl.mag - Relative temperature 0...99.99
9456 u16 10 .PDNS1MxRat.mag - PDNSPTOC1 ratio I2/I1 0...999.99 [%]
9457 u16 100 .Hz.mag - Frequency 30...80.00
[Hz]
9458 i16 100 .HzS.mag - Frequency gradient -/+10.00 [Hz/
s]
9459 i16 10 .CondN.mag - Coductance -/+-1000 [mS]
9460 i16 10 .SusN.mag - Susceptance -/+-1000 [mS]
2.5 Controls
Table 143: Explanations of the controls table columns
Column name
Description
0xA Coil (0X) address for control value.
CS Control structure and bit within the structure for control value.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Value Meaning of the written value.
2.5.1 Reset, acknowledge and trigger points (A)
Table 144: Reset, acknowledge and trigger points (A)
0xA
CS IEC 61850 name SA name Description Values
LD0.LLN0
2060 2.00 .LEDRs1.Oper.ctlVal Reset indications and LEDs 1=Reset
2061 2.01 .LEDRs2.Oper.ctlVal Reset Alarm LEDs 1=Reset
LD0.PEMSTA1
2062 2.02 .RecRs.Oper.ctlVal Reset Power max demands 1=Reset
LD0.DARREC1
Table continues on next page
Section 2 1MRS757822 B
Modbus data mappings
78 Recloser Protection and Control RER615
Point List Manual