BitA RegA IEC 61850 name SA name Description Values
2851 178.03 .OpNumAlm.stVal OPR_ALM CB operations alarm 1=Alarm
2852 178.04 .OpNumLO.stVal OPR_LO CB operations lockout 1=Lockout
2853 178.05 .LonTmAlm.stVal MON_ALM CB inactive alarm 1=Alarm
2854 178.06 .PresAlm.stVal PRES_ALM Low pressure alarm 1=Alarm
2855 178.07 .PresLO.stVal PRES_LO Low pressure lockout 1=Lockout
2856 178.08 .APwrAlm.stVal IPOW_ALM Lyt alarm 1=Alarm
2857 178.09 .APwrLO.stVal IPOW_LO Lyt lockout 1=Lockout
2858 178.10 .CBLifAlm.stVal CB_LIFE_ALM CB lifetime alarm 1=Alarm
2.3.61 LD0.TCSSCBR1 Trip circuit supervision (1)
Table 64: LD0.TCSSCBR1 Trip circuit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.TCSSCBR1
2780 173.12 .CirAlm.stVal ALARM Supervision alarm 1=Alarm
2781 173.13 .mcd
2.3.62 LD0.TCSSCBR2 Trip circuit supervision (2)
Table 65: LD0.TCSSCBR2 Trip circuit supervision (2)
BitA
RegA IEC 61850 name SA name Description Values
LD0.TCSSCBR2
2782 173.14 .CirAlm.stVal ALARM Supervision alarm 1=Alarm
2783 173.15 .mcd
2.3.63 LD0.SEQRFUF1 Fuse failure protection (1)
Table 66: LD0.SEQRFUF1 Fuse failure protection (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.SEQRFUF1
2996 187.04 .Str.general FUSEF_U Start 1=Start
2997 187.05 .mcd
2998 187.06 .Str3Ph.general FUSEF_3PH 3-phase start 1=Start
2999 187.07 .mcd