2.4.17 LD0.MDSOPT1 Generic operation time supervision
Since the register size is 16 bits, the value saturates at 65535 hours (approximately
7.5 years). Alternatively, a 32-bit user-definable register can be made of this data to
cover the whole 300 000 hours (34 years) range. The value can also, for example,
be rescaled to show “total operation days” instead by changing the scale factor
from 1 to 1/24 = 0.0417.
Table 108: LD0.MDSOPT1 Generic operation time supervision
RegA Type Scale IEC 61850 name SA name Description Values
2048 u16 1 .stVal OPR_TIME Operating hours 0…299999
[hours]
2.4.18 LD0.CMMXU1 Phase current measurements (1)
Table 109: LD0.CMMXU1 Phase current measurements (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.CMMXU1 Phase current (1)
138 u16 1000 .A.phsA.instCVal.mag I_INST_A - phsA amplitude
0.00...40.0
[xIn]
139 u16 1000 .A.phsB.instCVal.mag I_INST_B - phsB amplitude
0.00...40.0
[xIn]
140 u16 1000 .A.phsC.instCVal.mag I_INST_C - phsC amplitude
0.00...40.0
[xIn]
2.4.19 LD0.CMSQI1 Sequence of current measurements (1)
Table 110: LD0.CMSQI1 Sequence of current measurements (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.CMSQI1 Sequence of currents
143 u16 1000 .SeqA.c1.instCVal.mag I1_INST - positive amplitude
0.00...40.0
[xIn]
144 u16 1000 .SeqA.c2.instCVal.mag I2_INST - negative amplitude
0.00...40.0
[xIn]
145 u16 1000 .SeqA.c2.instCVal.mag I3_INST - zero amplitude
0.00...40.0
[xIn]
2.4.20 LD0.RESCMMXU1 Residual current measurement (1)
Table 111: LD0.RESCMMXU1 Residual current measurement (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.RESCMMXU1 Residual current (1)
141 u16 1000 .A.res.instCVal.mag I0_INST - amplitude
0.00...40.0
[xIn]
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 61
Point List Manual