2.4.31 LD0.RESCMSTA1 Residual current demand value (1)
Table 122: LD0.RESCMSTA1 Residual current demand value (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.RESCMSTA1 Demand value
1989 u16 1000 .AvAmps.mag I_DMD_RES - residual amplitude
0.00...40.0
[xIn]
Update time stamp
1)
1990 u16 - - Year - month
1991 u16 - - Day - hour
1992 u16 - - Minute - second
1993 u16 - - Milliseconds
1994 u16 - - Time quality
1995 u16 1000 .MaxAmps.mag Max demand Io - Max Io demand
0.00...40.0
[xIn]
Update time stamp
1)
1996 u16 - - Year - month
1997 u16 - - Day - hour
1998 u16 - - Minute - second
1999 u16 - - Milliseconds
2000 u16 - - Time quality
1) See the technical manual.
2.4.32 LD0.CMSTA1 Phase current demand values (1)
Table 123: LD0.CMSTA1 Phase current demand values (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.CMSTA1 Demand value
2001 u16 1000 .AvAmpsA.mag I_DMD_A - phsA amplitude
0.00...40.0
[xIn]
2002 u16 1000 .AvAmpsB.mag I_DMD_B - phsB amplitude
0.00...40.0
[xIn]
2003 u16 1000 .AvAmpsC.mag I_DMD_C - phsC amplitude
0.00...40.0
[xIn]
Update time stamp
1)
2004 u16 - - Year - month
2005 u16 - - Day - hour
2006 u16 - - Minute - second
2007 u16 - - Milliseconds
2008 u16 - - Time quality
Table continues on next page