2.3.5 LD0.FDPHLPDOC1 Three-phase directional overcurrent
protection, low stage (1)
Table 8: LD0.FDPHLPDOC1 Three-phase directional overcurrent protection, low stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.FDPHLPTOC1
3006 187.14 .Str.general START General start 1=Start
3007 187.15 .mcd
3008 188.00 .Str.phsA phsA start 1=Start
3009 188.01 .mcd
3010 188.02 .Str.phsB phsB start 1=Start
3011 188.03 .mcd
3012 188.04 .Str.phsC phsC start 1=Start
3013 188.05 .mcd
3014 188.06 .Op.general OPERATE General operate 1=Operate
3015 188.07 .mcd
2.3.6 LD0.FPDHLPDOC2 Three-phase directional overcurrent
protection, low stage (2)
Table 9: LD0.FPDHLPDOC2 Three-phase directional overcurrent protection, low stage (2)
BitA
RegA IEC 61850 name SA name Description Values
LD0.FDPHLPTOC2
3016 188.08 .Str.general START General start 1=Start
3017 188.09 .mcd
3018 188.10 .Str.phsA phsA start 1=Start
3019 188.11 .mcd
3020 188.12 .Str.phsB phsB start 1=Start
3021 188.13 .mcd
3022 188.14 .Str.phsC phsC start 1=Start
3023 188.15 .mcd
3024 189.00 .Op.general OPERATE General operate 1=Operate
3025 189.01 .mcd
Section 2 1MRS757822 B
Modbus data mappings
20 Recloser Protection and Control RER615
Point List Manual