2.3.87 LD0.XAGGIO130 Physical I/O states (AIM card XA130)
Table 90: LD0.XAGGIO130 Physical I/O states (AIM card XA130)
BitA RegA IEC 61850 name SA name Description Values
LD0.XAGGIO130
3280 205.00 .Ind1.stVal XA130-Input 1 State 0/1=Off/On
3281 205.01 .mcd
3282 205.02 .Ind2.stVal XA130-Input 2 State 0/1=Off/On
3283 205.03 .mcd
3284 205.04 .Ind3.stVal XA130-Input 3 State 0/1=Off/On
3285 205.05 .mcd
3286 205.06 .Ind4.stVal XA130-Input 4 State 0/1=Off/On
3287 205.07 .mcd
2.4 Registers
Table 91: Explanations of columns in register tables
Column name
Description
RegA Default 3X and 4X register address for the data.
Type Type of the register. The alternatives are u16, u32 (unsigned 16 and 32 bits
integer) or i16, i32 (signed 16 and 32 bit integer).
Scale Scale factor as default. Also, an adjustable offset value exists that is set to 0 by
default.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Also, if a register is writable, it is stated here.
Values The value range of the original IEC 61850 value, that is, before scaling.
2.4.1 User definable registers [Alt.1], visible on 3x and 4x
Table 92: User definable registers [Alt.1], visible on 3x and 4x
RegA
Type Scale IEC 61850 name SA name Description Values
(0) Reg < not mappable- not visible >
1 Reg User Register 1
2 Reg User Register 2
3 : :
Table continues on next page