2.3.21 LD0.HAEFPTOC1 Harmonics-based earth-fault protection
(1)
Table 24: LD0.HAEFPTOC1 Harmonics-based earth-fault protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.HAEFPTOC1
3312 207.00 .Str.general START Stage start 1=Start
3313 207.01 .mcd
3314 207.02 .Op.general OPERATE Stage operate 1=Operate
3315 207.03 .mcd
2.3.22 LD0.NSPTOC1 Negative-sequence overcurrent protection
(1)
Table 25: LD0.NSPTOC1 Negative-sequence overcurrent protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.NSPTOC1
2956 184.12 .Str.general START Stage start 1=Start
2957 184.13 .mcd
2958 184.14 .Op.general OPERATE Stage operate 1=Operate
2959 184.15 .mcd
2.3.23 LD0.NSPTOC2 Negative-sequence overcurrent protection
(2)
Table 26: LD0.NSPTOC2 Negative-sequence overcurrent protection (2)
BitA
RegA IEC 61850 name SA name Description Values
LD0.NSPTOC2
2960 185.00 .Str.general START Stage start 1=Start
2961 185.01 .mcd
2962 185.02 .Op.general OPERATE Stage operate 1=Operate
2963 185.03 .mcd
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 25
Point List Manual