2.4.34 LD0.PEMMTR1 Three-phase energy measurements (1)
Table 125: LD0.PEMMTR1 Three-phase energy measurements (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.PEMMTR1
2037 u32 1 .SupWh.actVal Reverse active energy (high)
0...1E10
[kWh]
2038 .SupWh.actVal (low word)
2039 u32 1 .SupVArh.actVal Reverse reactive energy (high)
0...1E10
[kVAr]
2040 .SupVArh.actVal (low word)
2041 u32 1 .DemWh.actVal Forward active energy (high)
0...1E10
[kWh]
2042 .DemWh.actVal (low word)
2043 u32 1 .DemVArh.actVal Forward reactive energy (high)
0...1E10
[kVAr]
2044 .DemVArh.actVal (low word)
2.4.35 System diagnostic values
Table 126: System diagnostic values
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.LPHD1
2050 u16 1 .PhyHealth1.stVal Warning Last warning code
1)
2051 u16 1 .PhyHealth2.stVal Internal fault Last internal fault code
1)
DR.RDRE1
2052 u16 1 .FltNum.stVal Num.of DR recordings 0...N
2053 u16 1 .MemUsed.stVal DR memory used 0...100 [%]
LD0.LPHD1
2054 u16 1 .NumPwrUp.stVal Num of cold starts 0...65535
2055 u16 1 .WrmStr.stVal Num of warm starts 0...65535
2056 u16 1 .WacTrg.stVal Num of watchdog resets 0...65535
2057 u16 1 .NumCmpChg.stVal Num of conf. changes 0...65535
1) See the technical manual.
Section 2 1MRS757822 B
Modbus data mappings
68 Recloser Protection and Control RER615
Point List Manual