0xA CS IEC 61850 name SA name Description Values
2063 2.03 .RsRec.Oper.ctlVal Reset reclosing 1=Reset
2064 2.04 .RsCnt.ctlVal Reset reclosing counters 1=Reset
LD0.SSCBR1
2065 2.05 .RsAccAPwr.Oper.ctlVal Reset CB accum. energy 1=Reset
2066 2.06 .RsCBWear.Oper.ctlVal Reset CB wear data 1=Reset
DR.RDRE1
2067 2.07 .RcdTrg.Oper.ctlVal Trig DR recording 1=Trig
2068 2.08 .MemClr.Oper.ctlVal Clear DR memory 1=Clear
LD0.CMSTA1
2069 2.09 .RecRs.Oper.ctlVal Reset Max current1 demands 1=Reset
LD0.PEMMXU1
2070 2.10 .SupDmdRs.Oper.ctlVal Reset energy values 1=Reset
LD0.SCCBR1
2071 2.11 .RsTrvTm.Oper.ctlVal Reset CB travel time 1=Reset
2072 2.12 .RsSprChaTm.Oper.ctlV
al
Reset CB spring charge time 1=Reset
LD0.RESCMSTA1
2073 2.13 .RecRs.Oper.ctlVal Reset Io (1) max demands 1=Reset
LD0.RESVMSTA1
2074 2.14 .RecRs.Oper.ctlVal Reset Uo (1) max demands 1=Reset
2.5.2 LD0.LPHD1 IED warm reset (1)
Table 145: LD0.LPHD1 IED warm reset (1)
0xA
CS IEC 61850 name SA name Description Values
LD0.LPHD1
2080 3.00 .RsDev.Oper.ctlVal Warm reboot of IED 1=Reboot
2.5.3 CTRL.CBCSWI1 Circuit breaker (1) control
Table 146: CTRL.CBCSWI1 Circuit breaker (1) control
0xA
CS IEC 61850 name SA name Description Values
CTRL.CBCSWI1
2048 1.00 .Pos.Oper.ctlVal Select open 1=Select
2049 1.01 .Pos.Oper.ctlVal Select close 1=Select
2050 1.02 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2051 1.03 .Pos.Oper.ctlVal Execute selection 1=Execute
2052 1.04 .Pos.Oper.ctlVal Direct open 1=Open
2053 1.05 .Pos.Oper.ctlVal Direct close 1=Close
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 79