KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
229
10.24.3 General - Additional functions/objects
Options: Deactivated
Activated
This parameter enables additional functions and communication objects.
10.24.4 General — Delay time for read telegrams after reset [s]
Options: Setting option from 1 - 255 seconds
This parameter can be used to receive telegrams via the "Input" object. The received
telegrams are sent with the set delay time to the "Output" object after a reset.
Note
This parameter is only available if the "Additional function" parameter is set to
"Yes".
10.24.1 General - "Current HVAC operating mode" object active
Options: Deactivated
Activated
The parameter is used to specify whether the "Current HVAC operating mode" object is
activated.