KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
265
10.24.104 Temperature reading
10.24.105 Temperature reading — Inputs of temperature reading
Options: Internal measurement
External measurement
Weighted measurement
The room temperature can be measured at the device or fed to the device by an object via the
bus. In addition, weighted measuring is also available, in which the weighted average of up to
three temperature values (1 x internal, 2 x external) is calculated and used as an input value for
control.
10.24.106 Temperature reading — Inputs of weighted temperature reading
Options: Internal and external measurement
2 x external measurement
Internal and 2x external measurement
Specifies the temperature reading inputs for the weighted measurement, in which the calculated
weighted average of the inputs is used as an input value for control
Note
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Weighted measurement".
10.24.107 Temperature reading — Weighting of internal measurement (0 to 100%)
Options: Setting option between 0 - 100
Specifying the weighting of the internal measurement from 0 to 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement" or "Internal
and 2x external measurement".
10.24.108 Temperature reading — Weighting of external measurement (0 to 100%)
Options: Setting option between 0 - 100
Specifying the weighting of the external measurement from 0 to 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement", "2x external
measurement" or "Internal and 2x external measurement".