KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
244
10.24.38 Basic stage cooling
Notice
Only available when the "Extended settings" parameter under "Cooling control"
is activated.
10.24.39 Basic stage cooling — Status object cooling
Options: Deactivated
Activated
This parameter enables the "Status cooling" communication object.
10.24.40 Basic stage cooling — Mode of the control value
Options: Normal
Inverse
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
– Normal: Value 0 means "Valve closed".
– Inverse: Value 0 means "Valve open".
10.24.41 Basic stage heating - Control value difference for sending of heating control value
Options: 2%
5%
10%
Send cyclic only
The control values of the 0 - 100% PI continuous controller are not transmitted after every
calculation. Instead, they are transmitted when the calculation results in a value that is different
enough to the previous sent value to make a transmission meaningful. This value difference
can be entered here.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%,"PI PWM, On/Off“ or "Fan coil".
10.24.42 Basic stage cooling — Cyclic sending of the control value
Options: 00:01:00 - 01:00:00
The current control value used by the device can be cyclically transmitted to the bus.