KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
272
"Temperature limit of additional cooling stage".
– Setpoint temperature
– Hysteresis
– Integral component of PI controller
10.24.128 Temperature limiter - Setpoint temperature of cooling / additional cooling stage
Options: Setting option from 1 - 30
The parameter is used to specify the value of the setpoint temperature for "Cooling" or the
"Additional cooling stage".
10.24.129 Temperature limiter - Hysteresis
Options: Setting option between 0.5 - 5
The hysteresis specifies the fluctuation range of the controller around the setpoint value. The
lower switching point is located at "Setpoint value minus hysteresis" and the upper point is at
"Setpoint value plus hysteresis".
Notice
This parameter is only available when one or several of the following parameters
are activated.
"Temperature limit heating"
"Temperature limit additional heating stage"
"Temperature limit cooling"
Temperature limit additional cooling stage
10.24.130 Temperature limiter - Integral component of PI controller
Options: Keep
Reset
The parameter is used to specify whether the integral component of the PI controller is retained
or reset.