Publication 1756-UM523F-EN-P - December 2006
Update Modules and Redundant Systems 131
3. Open the SRM configuration tool for the
primary chassis.
A. Start RSLinx software.
B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the 1757-SRM module and choose Module Configuration.
4. Disqualify the secondary chassis, A. Click Configuration.
B. Set Auto-Synchronization to Never.
C. Choose Apply and then Yes.
D. Click Synchronization.
F. Click OK.
Action Details
E. Click Disqualify Secondary and then Yes.
The secondary chassis
is disqualified.