Publication 1762-UM001D-EN-P - March 2004
A-10 Specifications
Isolated
Groups
Group 1: Outputs 0 to
3
Group 2: Outputs 4 to
7
Group 1: Outputs 0
to 7
Group 1: Outputs 0
to 15
Group 1:
Outputs 0 to 3
Group 2:
Outputs 4 to 7
Group 1:
Outputs 0 to 7
Group 2:
Outputs 8 to 15
All 6 Outputs
Individually
Isolated.
Output Group
to Backplane
Isolation
Verified by one of the
following dielectric
tests: 1836V ac for 1
sec. or 2596V dc for 1
sec.
265V ac working
voltage (IEC Class 2
reinforced insulation)
Verified by one of the following dielectric
tests: 1200V ac for 1 sec. or 1697V dc for 1
sec.
75V dc working voltage (IEC Class 2
reinforced insulation)
Verified by one of the following dielectric tests:
1836V ac for 1 sec. or 2596V dc for 1 sec.
265V ac working voltage (IEC Class 2 reinforced
insulation)
Output Group
to Output
Group
Isolation
Verified by one of the
following dielectric
tests: 1836V ac for 1
sec. or 2596V dc for 1
sec.
265V ac working
voltage (IEC Class 2
reinforced insulation)
Not Applicable Verified by one of the following dielectric tests:
1836V ac for 1 sec. or 2596V dc for 1 sec.
265V ac working voltage (basic insulation)
150V ac working voltage (IEC Class 2 reinforced
insulation)
Vendor I.D.
Code
111111
Product Type
Code
777777
Product Code 119 101 1
03
1
20
1
21
124
Table A.14 Output Specifications
Spec. 1762-OA8 1762-OB8 1762-OB16 1762-OW8 1762-OW16 1762-OX6I
Table A.15 Relay Contact Ratings (1762-OW8 and 1762-OW16)
Maximum Volts Amperes Amperes Continuous Volt-Amperes
Make Break Make Break
240V ac 7.5A 0.75A
2.5A
(2)
1800 VA 180 VA
120V ac 15A 1.5A
2.5A
(1)
1800 VA 180 VA
125V dc
0.22A
(1)
1.0A
28 VA
24V dc
1.2A
(2)
2.0A
(1) For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the applied dc voltage. For example, 28 VA/48V dc =
0.58A. For dc voltage applications less than 14V, the make/break ratings for relay contacts cannot exceed 2A.
(2) 1.5A above 40°C.