236 Rockwell Automation Publication 1766-UM001I-EN-P - June 2015
Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)
Keep Alive Interval (x1 s)
This parameter specifies a time interval for TCP Keep Alive mechanism.
If the timer times out, the MicroLogix 1400 transmits a keep-alive message. The
keep-alive message is a DNP Data Link Layer status request
(FC_REQUEST_LINK_STATUS). If a response is not received to the
keep-alive message, the MicroLogix 1400 deems the TCP connection broken and
closes the TCP connection.
The valid range is 1 to 65535. Default value is 10.
Slave Node Address
This value is a node address of this DNP3 Slave.
The valid range is 0 to 65519. Default value is 1.
Local TCP Port Number
This value is used to configure Local TCP Port Number which is used for TCP
socket listening.
The valid range is 0 to 65535. Default value is 20000.
Local UDP Port Number
This value is used to configure Local UDP Port Number which is used for UDP
socket listening.
The valid range is 0 to 65535. Default value is 20000.
Diagnostic File Number
The diagnostic file number is used to store the diagnostics for the
troubleshooting of DNP3 Ethernet subsystem. The status of DNP3 TCP and
UDP subsystem is stores to this data file.
The value of this parameter is N file only. Valid range is 0, 7, 9 to 255. Default
value is 0.
See Diagnostics on page 320.

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1400 and is the answer not in the manual?

Allen-Bradley MicroLogix 1400 Specifications

General IconGeneral
Processor32-bit
Expansion ModulesUp to 7 expansion I/O modules
Power Supply24V DC or 120/240V AC
Programming SoftwareRSLogix 500
Communication PortsEthernet, RS-232/RS-485 combo port
Controller TypeProgrammable Logic Controller (PLC)
SeriesMicroLogix
Digital Outputs12
Analog Inputs6 (embedded)
Analog Outputs2 (embedded)
High-Speed Counter6 high-speed counters
Pulse Output2 (embedded)
Ethernet PortYes

Related product manuals